Circuitry |
Microcontroller 80C31 @ 8 MHz, 2 K RAM |
Level Measurement & Transmission |
Through optical encoder. |
Range |
0-19999 mm |
Accuracy |
+/- 1 mm |
Input |
From sprocket shaft of SBEM or any other make of tank level gauge |
Temperature Measurement & Transmission (optional) |
Using external temperature sensor |
Range |
-100.0 to +100.0° C |
Accuracy |
+/- 0.2° C |
Resolution |
+/- 0.1° C |
Sensor type |
Pt-100 Spot / Averaging (Multi-point). Maximum 14 points Selection through solid state electronic multiplexer |
Transmission to Communication Interface Unit |
2 Way / 2 wire RS 485 ASCII coded |
Transmission to Tank Side Indicator |
Serial RS 232C |
Baud rate |
1200 (standard) |
2400 (optional) |
Data Protection |
Longitudinal and vertical parity check. |
Inbuilt Display (Optional) |
4 ½ digit, ½" high, 7 segment LCD to display sequentially - Level in mm - Temperature in C - Alarm status and diagnostics |
Diagnostics |
In-built |
Power Supply |
110 VAC, ±10%, 50 Hz, 1 mains isolated, 4 VA |
Ambient Operating Temperature |
0 to +60° C |
Relative Humidity |
95% max. (non condensing) |
Transmitter Housing |
Cast Aluminium LM6 |
Protection |
Flameproof to IS/IEC 60079-1:2007, Zone 1, Gr. IIA & IIB |
Weatherproof IP65 as per IS/IEC |
Terminals for temperature sensor |
Intrinsically safe to IS 5780- temperature 1980, Ex ia IIA and IIB T6 |