Two Wire Transmitter |
Range |
8000 / 12000 / 16000 / 24000 mm |
Output |
4 – 20 mA DC |
Input Sensor |
3 wire, precision, multi turn wire wound potentiometer. |
Source voltage ( Vsource ) ( from external source ) |
Max. 36 VDC. |
Min. {12 + (0.02 x Loop resistance in Ω )} VDC. |
Minimum Span |
25 % of the range. |
Accuracy (Includes errors due to nonlinearity and Hysteresis.) |
± 0.75 % for measuring range below 6000 mm. |
± 0.50 % for measuring range above 6000 mm. |
Terminals |
Suitable for conductor size up to 2.5 mm2 |
LIMIT SWITCH |
|
Range (Factory Set) |
8000 / 12000 / 16000 / 24000 mm. |
Number of switches |
2 or 4 |
Range of Adjustment |
0-50% for LO & LO-LO |
50-100% for HI & HI-HI |
Repeatability |
± 20 mm |
Hysteresis (For 8000/12000/16000/24000 mm ranges |
40 / 55 / 70 / 100 mm respectively. |
Contact type & rating |
Micro switch, 5A @ 230 VAC or 2A @ 24 VDC (Resistive). |
Contact Configuration |
1 c/o (NO, NC, POLE ) per limit switch. |